HomeMy WebLinkAbout405.001 - Non-High Rise Standpipe Requirements
FIRE PREVENTION MANUAL
FIRE EXTINGUISHING SYSTEMS
405.001 NON-HIGH RISE STANDPIPE REQUIREMENTS
EFFECTIVE: AUGUST 2005
Current Revision Date: 5/21/19 Next Revision Date: 5/21/22
Author’s Name/Rank:
Byron Beagles
Fire Prevention Engineer Review Level: 1
Administrative Support:
Sherrie L. Badertscher
Management Analyst II
PURPOSE
This policy has been established to provide direction for the design, installation and
flow testing of standpipe systems for non-high rise buildings within the City of
Fresno (City) and contract service areas.
APPLICATION
This policy applies to the installation of standpipe systems in buildings not classified
by the California Building Code (CBC) as a highrise building. As allowed by National
Fire Protection Association (NFPA), Standard 14, Installation of Standpipe and Hose
Systems, standpipe systems in non-high rise building with fire pumps can be
designed for the required standpipe flow and pressure utilizing a supply coming from
a Fresno Fire Department (FFD or Department) pumper engine connected from a
fire hydrant to the building fire department connection (FDC). This policy is also
applicable to buildings that require standpipe systems, but a fire pump is not needed
for the fire sprinkler design. All standpipe systems are to be installed per this policy
and the latest California Fire Code (CFC) and CBC adopted edition of NFPA 14.
OPERATIONAL POLICY
For a typical multi-story non-high rise office or residential building, standpipe
demand as required by NFPA 13 will always exceed fire sprinkler demand.
Standpipe systems in modern building are nearly always combined with the fire
sprinkler piping system primarily as a cost savings. Such a standpipe system is
defined by the CFC as a “Class I, manual wet system” where a Department pumper
engine is needed to meet standpipe system demand. All fire pumps are required to
have check valves installed at the discharge of the fire pump and all FDC
connections to the fire sprinkler system must be made to discharge side of the
aforementioned check valve. When a fire pumper engine is pressurizing the fire
sprinkler/standpipe system the fire pump is therefore bypassed with the greater flow
and pressure of the larger pump. The fire sprinkler system design engineer is
therefore tasked with supplying both a fire sprinkler system demand hydraulic
Section 405.001
Page 1 of 4
calculation(s) utilizing the available public water flow and pressure supply with assist
from the building fire pump as applicable and a separate standpipe hydraulic
calculation utilizing a Department pumper engine as the sole water source.
OPERATIONAL GUIDELINES
Buildings that require standpipe systems are typically multi-story and have a
minimum of two (2) required stairways. For a building of this type, the simultaneous
flow and pressure demand for the design of the system is 500 gpm at 100 psi at the
two (2) upper most hydraulically remote standpipe outlets and 250 gpm at 100 psi at
the other stairway uppermost outlet. For building with more than two (2) stairways,
the additional stairwell standpipe has a demand of 250 gpm at 100 psi for the
uppermost outlet up to a total demand in a fire sprinklered building of 1000 gpm.
Additional stairs must also have standpipe systems but only the three (3) most
hydraulically remote stairway standpipes must be calculated.
Fire sprinkler system plan submittals and hydraulic calculations that include
standpipe systems are to include the following information:
1. Standpipe system hydraulic calculations are to use an FFD fire engine pump
as the supply source as an installed fire pump is bypassed when FFD is
pumping into the system. FFD fire engine pump curve is 1000 gpm at 150
psi.
2. Standpipe system hydraulic calculations are to originate at the fire department
connection with FFD pump data. The remaining portions of the calculations
are to be in accordance with the NFPA 14. Fire sprinkler system demand is
not required to be added to standpipe system demand.
3. Standpipe plans are to have the required class (Class I for most installations)
and Type (automatic wet or manual wet) of standpipe noted on the plans in
accordance with CFC definitions.
4. For buildings with roof slopes less than 4:12, each standpipe system stairway
riser is to be extended to 2-1/2 inch outlets on the roof. The most remote
standpipe is to be equipped with two (2), 2½ inch hose valves for standpipe
testing at the 500 gpm remote standpipe demand.
Section 405.001
Page 2 of 4
5. For buildings with roof slopes in excess of 4:12 the uppermost stair landing
standpipe outlet is to have an adjacent exterior openable window with a clear
opening area of a minimum 36” X 36” or a similar sized access panel located
no more than 36 inches above the landing level for the purposes of directing
flow test discharge. If such an opening cannot be provided, then a 3” drain
pipe discharging to the building exterior with 2-1/2” swivel female hose
coupling at the landing is required so that the flow test may be conducted
utilizing an in-line pitotless 2-1/2 inch flow testing instrument.
6. Provide at least one (1) hose valve installation detail on the plans. If using
pressure reducing hose valves, a drawing must be provided for the pressure
reducing hose valve and one (1) for a non-pressure reducing hose valve (if
installed).
7. Hose valves must be in-line hose valves and pressure gauge with isolation
valve must be installed before the hose valve. No angle valves are permitted.
8. Hose valves installed in stairwells are to have the hose valve installed on the
floor level stair landing.
9. The minimum supply pipe size for combined fire sprinkler/standpipe systems
is to be 4 inch. Note that for some building designs, a 6 inch ground floor
supply pipe to the most remote stairwell carrying the 500 gpm demand may
be needed to overcome the friction loss.
10. Standpipe supply mains are to be provided with supervised and indicating
control valves so that a single stairway standpipe riser can be taken out of
service for maintenance without placing the remaining standpipe risers out of
service.
11. For fire sprinkler systems combined with standpipe systems, fire sprinkler
system connections for each floor are only to be supplied from one (1) of the
standpipe risers. Cross connecting fire sprinkler laterals significantly
complicates flow switch testing and is not permitted.
12. Each fire sprinkler lateral from a combined standpipe riser is to be provided
with a supervised floor control valve, check valve, drain valve, and supervised
water flow switch assembly.
13. For standpipe systems having a demand up to 750 gpm, a standard 2-way
FDC is acceptable. For demands in excess of 750 gpm, the FDC is to be a
single 4-1/2 swivel female National Hose Thread (NHT) connection.
14. In every case, the Fire Marshal, or designee, has the authority to modify
these requirements and the determination is to be made at the sole discretion
of the Fire Marshal, or designee.
Section 405.001
Page 3 of 4
Class I, manual wet standpipe systems are required to be hydraulically calculated to
provide the minimum flow and pressure specified in NFPA 14. The required
acceptance and 5-Year flow test procedure is to be in accordance with the test
procedures specified in Fire Prevention Manual, Five Year Test for Combined
Standpipes Form, FPD-F-17. NFPA 14 allows the local authority having jurisdiction
(AHJ) to modify the required flow test procedures to achieve the intent of the
standard. FPD-F-17 provides alternative test procedures utilizing the fire pump
specified for the fire sprinkler system design or where a fire pump is not installed, a
method to utilize the available water supply from the public water main infrastructure.
DEFINITIONS
This section intentionally left blank.
PROCESS
This section intentionally left blank.
INFORMATION
This section intentionally left blank.
CROSS-REFERENCES
California Building Code, Current edition
California Fire Code, Current edition
National Fire Protection Association Standard (NFPA)
NFPA 14, Installation of Standpipes and Hose Systems, Current edition
Fire Prevention Manual
Five Year Test for Combined Standpipes Form, FPD-F-17
Section 405.001
Page 4 of 4