HomeMy WebLinkAbout403.003 - Fire Hydrant Spacing, Installation and Fire Flow Requirements
FIRE PREVENTION MANUAL
DEVELOPMENT REQUIREMENTS
403.003 FIRE HYDRANT SPACING, INSTALLATION &
FIRE FLOW REQUIREMENTS
EFFECTIVE: JUNE 2008
Current Revision Date: 2/13/19 Next Revision Date: 2/13/22
Author’s Name/Rank:
Byron Beagles,
Fire Prevention Engineer Review Level: 1
Administrative Support: Sherrie L. Badertscher, M.A. II
PURPOSE
The purpose of this policy is to establish the requirements for fire hydrant spacing,
installation, and minimum water flows (i.e., fire flow) and pressures for firefighting.
APPLICATION
This policy applies to those who may be installing fire hydrants within the City of
Fresno and the Fresno Fire Department’s (FFD or Department) contract service
areas.
OPERATIONAL POLICY
A. General Requirements:
1. Fire hydrants will be installed and maintained in service prior to delivery of
combustible material to the jobsite and during all subsequent phases of
construction.
2. Fire hydrants will be installed in accordance with City of Fresno Public
Works Standards with not less than a minimum eight (8”) inch water
supply, unless otherwise specified below. Private fire hydrants
installations may utilize any American Water Works Association (AWWA)
approved dry barrel/top operating nut style hydrant model comparable to
the current Public Works Standard W-3 style hydrant in use by the Water
Division; wet barrel hydrants are no longer permitted in new water main
system installations due to the potential property damage and water
conservation concerns on private property. All hydrants will have a single
4-1/2 inch and two 2-1/2 inch NST/NHT threaded outlets.
Section 403.003
Page 1 of 6
3. Fire hydrant installation at the end of cul-de-sacs or dead end roads
should be avoided wherever possible. Install fire hydrants at ½ the
required fire hydrant spacing from the end of the street or drive aisle.
4. All fire hydrants will have an isolation gate valve installed in the lateral
water line from the primary supply main. For private hydrants, the lateral
may be reduced to six (6”) inch provided the length does not exceed 50
feet. The isolation gate valve in the lateral will not be located within a
parking stall or a loading zone. If located in a landscape area, the valve
lid will be installed with a minimum 12” X 12” concrete pad.
5. Private fire hydrants will be located between 30” and 72” (as measured to
hydrant centerline) from the face of a minimum six (6”) inch curb or edge
of road or wedged curb and provided with bollard protection per Public
Works Standard W-23. The 4-1/2 inch outlet will face the fire access road
and a 36 inch working space provided around the hydrant with the
exception of W-23 bollards.
6. Private fire hydrants will be located so that all building openings are within
500 feet of a hydrant (300 foot maximum driving distance plus 200 foot
hose pull from a fire engine).
7. Subject to the approval of the Fire Marshal, or designee, for large
industrial developments with fire pumps and high demand fire sprinkler
systems, private hydrants may be located downstream of the fire pump.
The fire department connection for the system will be located adjacent to
the public street to facilitate fire engine connection to a normal pressure
public hydrant to bypass the fire pump and pressurize the private high
pressure fire protection water main. The private fire protection water main
installer will paint the entire body of each high pressure hydrant in the
shade Pantone 288C Blue.
8. As required by the City of Fresno Water Division, the minimum backflow
prevention requirement for four (4”) inch and larger fire services is a single
detector check at property line in a vault and installed per Public Works
Standards W-16, 17, & 18. Fire protection systems proposed with AFFF,
other fire suppression agents, or other additives not approved for use in
domestic water systems will be protected with an approved reduced
pressure backflow double detector check assembly.
9. Installation of private fire protection water mains will be in accordance with
the latest adopted edition of National Fire Protection Association (NFPA)
13 and 24, the California Fire Code, and the requirements of this policy.
Section 403.003
Page 2 of 6
10. All private fire service underground systems will be provided with isolation
gate valves so that repairs of any portion of the private main will not shut
off more than five (5) fire appurtenances (fire hydrants and individual fire
sprinkler risers). Such valves must be the post indicator type (PIV) and be
electronically supervised to an approved fire alarm monitoring central
station service. The installing contractor will provide conduit in the trench
back to a central location on site where the fire alarm monitoring panel is
located for PIV and individual fire sprinkler water flow and riser control
valve supervision.
11. All fire protection water mains will have minimum 18 gauge blue tracer
wire installed in the trench.
12. For a single source private fire service water main with service taken from
a ten (10”) inch or larger circulated public water main and when a
minimum fire flow of 1500 gpm is required, the maximum allowable dead
end run of eight (8”) inch fire main to the most remote fire hydrant is 1000
feet (including equivalent feet of fitting losses). A single eight (8”) inch
service that transitions on site to a looped piping configuration may be
subject to verification of friction loss at the most remote hydrant with
hydraulic calculations by the design engineer of record.
13. For fire services where a 1500 gpm fire flow is required and the service is
taken from a ten (10”) inch or larger circulating public water main, the fire
service, detector check, and private main size may be reduced to six (6”)
inch if the distance from private hydrant to the public main is 200 feet or
less with the least number of direction changes possible.
14. For other than C-16 fire sprinkler contractors, fire service underground
plans will be submitted to and installation permits obtained from the City of
Fresno’s Building and Safety Division. Site utility plans with fire protection
water mains are routed to Fire Prevention for review and approval. All
field inspections of fire service undergrounds including the required full
flow flushing will be conducted by Building and Safety for permits they
issue.
B. Fire Flow and Hydrant Spacing Requirements:
Required fire flow is water available for fire suppression purposes above peak
domestic water demand at a residual pressure of 20 psi at the hydrant as
calculated using the methods describe in NFPA 291. Under the authority of
the California Fire Code (CFC), Sections 507.3, Fire Flow, and 507.5, Fire
Hydrant Systems, the Department has specific local fire flow and hydrant
spacing requirements as follows:
Section 403.003
Page 3 of 6
1. Single-Family Dwellings and Multi-family Dwellings up to 4 Units per
Building:
Required public and private hydrant fire flow is 1500 gpm minimum
with a maximum fire hydrant spacing of 600 feet.
In sub-divisions were streets with medians in accordance with Public
Works Standard P-57 are proposed, fire hydrants will be located at the
intersections of the maximum allowed street length of 600 feet.
2. Multi-Family Dwellings Development (Condominiums, Apartments, Hotels,
and Motels more than 4 units per building):
Public hydrant fire flow is 2500 gpm minimum with a maximum hydrant
spacing of 450 feet.
With the installation of either an NFPA 13 or NFPA 13R fire sprinkler
system in each building, private hydrant fire flow may be reduced to
1500 gpm with a maximum spacing of 600 feet. Non-fire sprinklered
community buildings and other structures not required to be fire
sprinklered by the local fire sprinkler ordinance can also utilize this fire
flow.
Under certain conditions and subject to review and approval by the
Fire Department and the Water Division for one (1) and two (2) story
multi-family residential development, a combination water system for
domestic and fire protection (hydrants and fire sprinkler supply) with
Water Division installed UL/FM fire protection approved water meter(s)
may be utilized. Reduced pressure backflow devices will not be
allowed on this type of service due to the inherent friction loss of these
devices having a negative impact on available water pressure for fire
hydrant and fire sprinkler system design.
3. Commercial, Industrial, and Institutional Development:
Public hydrant fire flow is 2500 gpm minimum with a maximum hydrant
spacing of 450 feet.
For public fire hydrant installation in the Downtown Planning Area
bounded by Freeways 41, 99, and 180, the required minimum fire flow
is 3500 gpm for zero lot line multistory development. The Fire
Marshal, or designee, has the authority to also require this fire flow in
other areas of the city that are proposed for similar high density
development.
Section 403.003
Page 4 of 6
With the installation of an NFPA 13 or City of Fresno Reduced
Hydraulic Demand Fire Sprinkler Design (See Fire Prevention Manual,
Section 405.012, Reduced Hydraulic Demand Sprinkler System
Design) fire sprinkler systems, private fire hydrant flow may be reduced
to 1500 gpm with a maximum spacing of 600 feet.
The Fire Marshal, or designee, is authorized to specify an increased
fire flow for certain high hazard occupancies such as, but not limited to,
petroleum tank farms, aircraft hangers, flammable liquid/chemical
manufacturing plants, and other high hazard uses.
OPERATIONAL GUIDELINE
This section left intentionally blank.
PROCESS
This section left intentionally blank.
INFORMATION
This section left intentionally blank.
DEFINITIONS
This section left intentionally blank.
CROSS REFERENCES
City of Fresno Department of Public Works Standard Drawings
California Fire Code
Section 507.3, Fire Flow
Section 507.5, Fire Hydrant Systems
National Fire Protection Association
NFPA 13
NFPA 13R
NFPA 24
NFPA 291
Section 403.003
Page 5 of 6
Fire Prevention Manual
Section 405.012, Reduced Hydraulic Demand Sprinkler System Design
Section 403.003
Page 6 of 6