HomeMy WebLinkAbout405.035 - NFPA 13D Hydraulic Calculations
Effective Date: January 2011 Justin Beal, Fire Prevention Engineer
Current Revision Date: 4/18/2023 Section 405.035
Next Revision (3) Date: 4/18/2027 Page 1 of 2
Fresno City Fire Department
400 Fire Prevention Manual
SECTION 405.035 NFPA 13D HYDRAULIC CALCULATIONS
PURPOSE
The purpose of this policy is to clarify the Fresno Fire Department’s (FFD or
Department) requirements related to preparing fire sprinkler systems designed for
one- and two-family dwellings in accordance with National Fire Protection Association
(NFPA) 13D – Standard for the Installation of Sprinkler Systems in One- and Two-
Family Dwellings (current edition with California amendments).
APPLICATION
This policy applies to all one- and two-family dwellings that will be equipped with a fire
sprinkler system within the Department’s service area, including contract service
areas. These requirements apply to both required and voluntary fire sprinkler
systems.
OPERATIONAL POLICY
Based upon the need for uniformity in application across the Department’s diverse
service delivery area, and after careful deliberation, the Department has determined
the following:
1. Due to the lower water pressures experienced by water purveyors in the
Department’s service delivery area, every fire sprinkler system to be
installed in a one- or two-family dwelling must be provided with hydraulic
calculations in accordance with NFPA 13D.
2. The use of NFPA 13D, §10.1.2 is prohibited. Designers and contractors
must use the Department’s prescriptive water supply curves for fire
sprinkler design as the design basis for all fire sprinkler systems,
including those designed under NFPA 13D. Designers and contractors
must contact the Department to obtain this information, prior to
submitting a permit application.
3. The use of any NFPA 13D section which uses a prescriptive pipe sizing
method is prohibited.
Effective Date: January 2011 Justin Beal, Fire Prevention Engineer
Current Revision Date: 4/18/2023 Section 405.035
Next Revision (3) Date: 4/18/2027 Page 2 of 2
4. When a single sprinkler head is protecting a single room and the spacing
is different from that shown on the required two head calculation, the
designer must also provide a single head hydraulic calculation.
OPERATIONAL GUIDELINE
This section intentionally left blank.
PROCESS
This section intentionally left blank.
INFORMATION
As noted in the Fresno Municipal Code (FMC), §10-50103.4, Responsibility for
Enforcement, the fire code official is responsible for the enforcement of building
standards and fire protection requirements relating to one- and two-family dwellings.
Additionally, per the California Fire Code (CFC) and California Residential Code
(CRC), the fire code official has the authority to formulate policies they deem
necessary based upon local conditions related to fire sprinkler systems in one- and
two-family dwellings.
DEFINITIONS
This section intentionally left blank.
CROSS-REFERENCES
California Fire Code (CFC), Current edition
California Residential Code (CRC), Current edition
Fresno Municipal Code (FMC)
Section 10-50103.4, Responsibility for Enforcement
National Fire Protection Association (NFPA) - 13D,
Standard for the Installation of Sprinkler Systems in One- and Two- Family
Dwellings (current edition with California amendments)