HomeMy WebLinkAbout405.030 - Specific Application Window SprinklersEffective Date: January 2010 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 7/1/2025 Section 405.030 Next Revision Date: 7/1/2028 Page 1 of 3 Fresno City Fire Department 400 Prevention Manual SECTION 405.030 SPECIFIC APPLICATION WINDOW SPRINKLERS PURPOSE The purpose of this policy is to clarify the Fresno Fire Department’s (FFD or Department) requirements for the installation of water curtains. APPLICATION This policy applies to all buildings equipped with an automatic fire sprinkler system within the Department’s service delivery area, including contract service areas. These requirements apply to both required and voluntary systems. OPERATIONAL POLICY Based upon the need for uniformity in application across the Department’s diverse service delivery area, and after careful deliberation, the Department has determined the following: 1. All proposed water curtains are required to use Tyco WS specific application window sprinklers. No other sprinklers will be permitted to be used in this application regardless of their listing. 2. Tyco WS specific application window sprinklers require sprinklers and piping on both sides of the water curtain in accordance with their listing. 3. All water curtain supply piping is required to be on its own riser, with a permanent and durable sign indicating its function. The water curtain riser must also include a separate, supervised control valve, water flow switch, alarm bell and drain. Installation of these components shall be accordance with National Fire Protection Association (NFPA) 13, Standard for the Installation of Fire Sprinkler Systems. Water curtain sprinkler systems are commonly used as an alternate, equivalent means of fire protection for fire resistance rated construction, and as such, the water curtain must remain in service, even if the standard automatic fire sprinkler system must be taken out of service for any reason. Effective Date: January 2010 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 7/1/2025 Section 405.030 Next Revision Date: 7/1/2028 Page 2 of 3 4. Any proposed water curtain installation must show a complete section detail of the installation on the fire sprinkler construction documents. This detail must show fire sprinkler head positions, window style to be protected, mullions or butt joints, etc. 5. Any proposed water curtain installation must include a note on the construction documents that the automatic fire sprinkler system spare fire sprinkler head kit must include water curtain fire sprinkler heads. The spare fire sprinkler head legend must show the correct fire sprinkler heads and counts. 6. All water curtains must comply with the requirements of NFPA 13, for fire sprinkler protected glazing. OPERATIONAL GUIDELINE This section intentionally left blank. PROCESS This section intentionally left blank. INFORMATION As noted in the currently adopted version of the California Fire Code (CFC), the fire code official has the authority to formulate policies they deem necessary based upon local conditions related to fire sprinkler installations. Currently, Tyco WS specific application window sprinklers are listed for use, subject to specific conditions, including a number of installation requirements, under International Code Council Evaluation Service (ICC-ES), ESR 2397 (Rev. May 2025). DEFINITIONS This section intentionally left blank. CROSS-REFERENCES California Fire Code, Currently adopted edition National Fire Protection Association (NFPA) 13, Currently adopted edition Effective Date: January 2010 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 7/1/2025 Section 405.030 Next Revision Date: 7/1/2028 Page 3 of 3 International Code Council Evaluation Service (ICC-ES), ESR 2397 (Rev. May 2025) TYCO, Product Listing TFP620