HomeMy WebLinkAbout405.020 - CPVC Hanger Spacing Section 405.020 Page 1 of 2 FIRE PREVENTION MANUAL FIRE EXTINGUISHING SYSTEMS 405.020 CPVC HANGER SPACING EFFECTIVE: SEPTEMBER 2013 Current Revision Date: 3/1/22 Next Revision Date: 3/1/25 Author’s Name/Rank: Scott T. Recchio, Fire Prevention Engineer Review Level: 1 Administrative Support: Noemi E. Rogers-Rodriguez, Management Analyst II ADA PURPOSE The purpose of this policy is to clarify the Fresno Fire Department’s (FFD or Department) requirements regarding the required two (2) point restraint pipe hanger installation locations and distances for fire sprinkler systems utilizing CPVC piping. APPLICATION This policy applies to all fire sprinkler systems within the Department’s service area, including contract service areas. This requirement applies to both required and voluntary fire sprinkler systems. OPERATIONAL POLICY This section intentionally left blank. OPERATIONAL GUIDELINE Based on the need for uniformity in application across the Department’s diverse service delivery area, and after careful deliberation, the Department has determined the following: The following diagram notes the required two (2) point restraint pipe hanger locations and distances for fire sprinkler systems utilizing CPVC piping: Section 405.020 Page 2 of 2 Hangers are required to be spaced an equal distance from the “T”, not to exceed the required overall spacing in currently adopted version of National Fire Sprinkler Association (NFPA) 13, 13D, and 13R. PROCESS This section intentionally left blank. INFORMATION This policy was developed to eliminate confusion for system installers and provides the best method for installation regardless of pipe manufacturer. DEFINITIONS For purpose of this policy, a hanger is defined as “a device or assembly used to support the gravity load of the system piping.” CROSS REFERENCES National Fire Protection Association (NFPA) 13, 13D, 13R Currently adopted edition