Loading...
HomeMy WebLinkAbout405.018 - Sprinkler Piping Under One Inch in DiameterEffective Date: March 1999 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 1/31/2025 Section 405.018 Next Revision (1) Date: 1/31/2028 Page 1 of 3 Fresno City Fire Department 400 Prevention Manual SECTION 405.018 SPRINKLER PIPING LESS THAN ONE INCH IN DIAMETER PURPOSE The purpose of this policy is to clarify the Fresno Fire Department’s (FFD or Department) requirements related to existing automatic fire sprinkler system piping which is less than one (1”) inch in diameter. APPLICATION This policy applies to all fire automatic sprinkler systems within the City of Fresno (COF) and contract service areas and includes both required and voluntary systems. This policy does not include automatic fire sprinkler systems installed in one-and two -family dwelling units, or where automatic fire sprinkler systems were installed per the requirements of National Fire Protection Association (NFPA) Standard 13D - Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes. OPERATIONAL POLICY Based upon the need for uniformity in application across the Department’s diverse service delivery area, and after careful deliberation, the Department has determined that during every automatic fire sprinkler system 5-year inspection where three-fourths (3/4”) inch piping is installed in the system, the following requirements shall apply: 1. If the three-fourths (3/4”) inch pipe is at the highest elevation of an upward sloping branch line, the contractor must remove and inspect one (1) of every ten (10) sprinkler system branch lines. If corrosion or other concerns are noted in more than three (3) pipe segments, all three- fourths (3/4) inch pipe in the system must be removed and inspected. 2. If the three-fourths (3/4”) inch pipe is at the lower elevation of an upward sloping branch line, or on a horizontal branch line, the contractor must remove and inspect one (1) of every four (4) branch lines. If corrosion or other concerns are noted in more than three (3) pipe segments, all three- fourths (3/4) inch pipe must be removed and inspected. 3. At least three (3) drops and/or tailbacks, on separate sprinkler branch lines, must be removed and inspected for corrosion and sediment. If either corrosion or sediment is located, all three-fourths (3/4) inch pipe must be removed and inspected. Effective Date: March 1999 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 1/31/2025 Section 405.018 Next Revision (1) Date: 1/31/2028 Page 2 of 3 4. Piping which is found to have its cross-sectional flow area reduced by a significant amount as determined by the Fire Marshal (or designee) shall be replaced. If more than half of the pipe inspected is found to have its cross- sectional flow area reduced by a significant amount as determined by the Fire Marshal (or designee) all three-fourths (3/4”) inch pipe, related fittings, sprinkler heads, etc. must be replaced (with a permit) with one inch (1”) pipe. OPERATIONAL GUIDELINE This section left intentionally blank . PROCESS This section intentionally left blank. INFORMATION As noted in the California Fire Code (CFC), the fire code official has the authority to formulate policies they deem necessary based upon local conditions related to all fire sprinkler systems and equipment. At one time, three-fourths (3/4”) inch diameter piping was considered acceptable to serve a single, fire sprinkler head in an automatic fire sprinkler system. Although this smaller diameter pipe loses three (3) pounds of pressure per square inch (psi) over ten (10’) feet of run of pipe for a light hazard occupancy application (0.76 psi for 1- inch pipe), there is no need to replace three-fourths (3/4”) inch piping that has not had its cross-sectional flow area reduced. After an automatic fire sprinkler system reaches fifty (50) years of age (and coinciding with the systems normal 5-year inspection), all three-fourths (3/4) inch sprinkler pipe within an automatic fire sprinkler system must be detached and its interior inspected to determine if its cross-sectional flow area has been reduced by corrosion, scale, etc. DEFINITIONS This section intentionally left blank. Effective Date: March 1999 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 1/31/2025 Section 405.018 Next Revision (1) Date: 1/31/2028 Page 3 of 3 CROSS-REFERENCES National Fire Protection Association (NFPA) Standard 13D, Standard for the Installation of Sprinkler Systems in One-and Two-Family Dwellings and Manufactured Homes, Currently adopted edition California Fire Code, Currently adopted edition.