Loading...
HomeMy WebLinkAbout405.013 - Inspectors Test Valves and Air VentsEffective Date: June 2006 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 1/31/2025 Section 405.013 Next Revision (1) Date: 1/31/2028 Page 1 of 3 Fresno City Fire Department 400 Prevention Manual SECTION 405.013 INSPECTORS TEST VALVES & AIR VENTS PURPOSE The purpose of this policy is to clarify the Fresno Fire Department’s (FFD or Department) requirements related to related to the design and installation of inspector’s test valves and air vents for automatic fire sprinkler systems. APPLICATION This policy applies to all automatic fire sprinkler systems within the City of Fresno (COF) and contract service areas and includes both required and voluntary systems. OPERATIONAL POLICY Based upon the need for uniformity in application across the Department’s diverse service delivery area, and after careful deliberation, the Department has determined that all, new automatic fire sprinkler systems shall conform to all of the following requirements: 1. Every automatic fire sprinkler system is required to have an approved inspector’s test valve/connection and air vent installed as noted in the currently adopted version of National Fire Protection Association (NFPA) 13 – Standard for the Installation of Sprinkler Systems. Both the test valve/connection and air vent must be shown on the construction documents noted in the California Fire Code (CFC). 2. The inspector’s test valve must be located at the end of the most hydraulically remote branch line, or other FFD approved location, not more than seven (7’) feet from the finished floor. 3. Where approved and installed above a ceiling, the inspector’s test valve must have an approved sign installed in accordance with Fire Prevention Manual, §402.016, Fire Department Required Signage. Effective Date: June 2006 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 1/31/2025 Section 405.013 Next Revision (1) Date: 1/31/2028 Page 2 of 3 4. When installed in combination, the inspector’s test valve and air vent piping assembly must be installed as noted in figure 405.013(a) below: 5. All inspector’s test valves for all group “R” occupancies must be placed in an FFD approved location which does not require entry into a dwelling or dwelling unit to operate the valve. OPERATIONAL GUIDELINE This section intentionally left blank. PROCESS This section intentionally left blank. Effective Date: June 2006 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 1/31/2025 Section 405.013 Next Revision (1) Date: 1/31/2028 Page 3 of 3 INFORMATION As noted in the CFC, the fire code official has the authority to formulate policies they deem necessary based upon local conditions related to all automatic fire sprinkler system installations. Inspectors test valves installed as noted in the currently adopted version of NFPA 13 are a more realistic and accurate test of the required alarm actuation requirements and are a convenient method to bleed trapped air from a fire sprinkler system. DEFINITIONS This section intentionally left blank. CROSS-REFERENCES National Fire Protection Association (NFPA) 13, Currently adopted edition California Fire Code, Currently adopted edition Fire Prevention Manual, §402.016, Fire Department Required Signage