HomeMy WebLinkAbout405.006 - Dry Standpipes - Five-Year Test PREVENTION MANUAL FIRE EXTINGUISHING SYSTEMS 405.006 DRY STANDPIPES - FIVE YEAR TEST (5-Year) EFFECTIVE: JANUARY 2009 Current Revision Date: 03/18/19 Next Revision Date: 3/18/22 Author’s Name/Rank: Byron H. Beagles Fire Prevention Engineer Review Level: 1 Administrative Support: Sherrie L. Badertscher Management Analyst II PURPOSE The material below is intended to document the minimum 5-year test inspection requirements for dry standpipe systems. APPLICATION This policy and the associated Dry Standpipes form, FPD-F-16, are to be used by contractors conducting dry standpipe 5-year testing. OPERATIONAL POLICY When it is necessary to use water temporarily in connection with any type of construction or other operation at a place where supply is inadequate for such purposes, application may be made to the City of Fresno (City) Water Division for a permit to use water from a fire hydrant. No person other than a duly authorized employee of the City will use water from, or connect any apparatus to, a fire hydrant without first obtaining a permit from the Water Division and securely attaching such permit to the fire hydrant at a conspicuous place near the point of connection. Each permit will specify the fire hydrant or hydrants authorized to be used and no person will attach such permit to any other hydrant, nor will any person remove, obliterate, deface, or obscure any permit. No person other than a duly authorized employee of the City will attach to the operating stem or cap of a fire hydrant any wrench or tool that is not approved by the Water Division for use on fire hydrants. Section 405.006 Page 1 of 3 Any permit, wrench, connecting apparatus, valve, hose, or other apparatus attached to a fire hydrant in violation of this section will be subject to removal and confiscation by the City. The applicable water rate, determined as specified in Fresno Municipal Code (FMC), Section 6-504, Type of Service, will be doubled for water used in violation of this section, subject to the minimum charge designated in the Master Fee Schedule (MFS). No permit or additional permit will be issued to any person who is in violation of this section until all such charges have been paid. OPERATIONAL GUIDELINE The Dry Standpipes form, FPD-F-16, is to be completed by any contractor performing testing on dry standpipe systems. PROCESS This section left intentionally blank. INFORMATION PERSONNEL/EQUIPMENT REQUIRED FOR DRY STANDPIPE 5-YEAR TEST Two personnel Pump capable of delivering at least 100 gpm at necessary pressure Air pump Calibrated gauges supplied by the contractor for all readings Supply of replacement gaskets for outlets Hydrant wrench Fire hose as needed Underwriters’ playpipe with 1-1/8-inch tip In-line gauge for use with 2-1/2-inch hose Second in-line gauge for use with 2-1/2-inch hose, or a pitot tube and gauge Necessary forms Tarps, diffusers, etc., to protect roof surface Two two-way radios are recommended to facilitate communications on high- rise buildings Compliance with Fresno Municipal Code (FMC), Section 6-534, Use of Fire Hydrants Regulated. DEFINITIONS This section left intentionally blank. Section 405.006 Page 2 of 3 CROSS-REFERENCES Fire Prevention Manual Dry Standpipes Form, FPD-F-16 Fresno Municipal Code (FMC) Section 6-504, Type of Service Section 6-534, Use of Fire Hydrants Regulated Section 405.006 Page 3 of 3