HomeMy WebLinkAbout405.040A - VICTAULIC BRAND FL-SC-VS2 Flexible Fire SprinklersEffective Date: April 2023 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 04/18/2023 Section 405.040A Next Revision (1) Date: 04/18/2026 Page 1 of 4 Fresno City Fire Department 400 Fire Prevention Manual SECTION 405.040A VICTAULIC BRAND FL-SC/VS2 FLEXIBLE FIRE SPRINKLERS PURPOSE This policy has been established to provide direction to contractors/designers for the design, use and installation of Victaulic brand FL-SC/VS2 flexible fire sprinklers. APPLICATION This policy applies to all fire sprinkler system installations, including required and voluntary systems. OPERATIONAL POLICY The Fresno Fire Department (FFD or Department) is permitted to specify requirements for the design, use, and installation of fire sprinklers for all fire sprinkler systems, as stated in the most recent edition of the California Fire Code (CFC). OPERATIONAL GUIDELINE Based upon the need for uniformity in application across the Department’s diverse service delivery area, the Department has determined that when contractors/designers intend to design, use, and install Victaulic brand FL-SC/VS2 flexible fire sprinklers in fire sprinkler systems, they must follow the requirements noted below: Contractors/designers may use the “Under 20 head TI” permit process for the installation of Victaulic brand FL-SC/VS2 flexible fire sprinklers. The Citizen Access portal is found at https://lmsaca.fresno.gov/CitizenAccess/Default.aspx. When completing the electronic permit application, the contractor/designer must enter the following information at Step 2: Records Details, Permit Info, in the “Detailed Description” field: 1. Victaulic brand FL-SC/VS2 flexible fire sprinklers will be used, Effective Date: April 2023 Author: Justin H. Beal, Fire Prevention Engineer Current Revision Date: 04/18/2023 Section 405.040A Next Revision (1) Date: 04/18/2026 Page 2 of 4 2. Victaulic sprinkler SIN, 3. Orientation, 4. Escutcheon, 5. Temperature rating, 6. Length, 7. Maximum number of bends to be used, 8. Victaulic VicFlex bracket assembly to be used. For installations using Victaulic brand FL-SC/VS2 flexible fire sprinklers, the contractor shall also include a complete copy of the latest version of the Victaulic FL-SC/VS2 flexible fire sprinkler manufacturer data sheets. This information shall be uploaded to the record at Step 2: Record Details, Attachments, by selecting the add button. Please read the information on the document file types permitted and the naming requirements for the documents. Effective Date: April 2023 Author: Justin H. Beal, Fire Prevention Engineer Current Revision Date: 04/18/2023 Section 405.040A Next Revision (1) Date: 04/18/2026 Page 3 of 4 Field Inspection Requirements It is the applicant/installing contractor's obligation, as with any fire sprinkler system field inspection, to have all required permit documents on site (see FFD Industry Bulletin 22-001). If all the required documents are not present upon arrival at the inspection site, FFD staff will discontinue the inspection, and a reinspection fee will be assessed, as has been FFD’s past practice. It is the obligation of the applicant/installing contractor to contact FFD to reschedule an additional inspection. PROCESS This section intentionally left blank. INFORMATION It is the applicant/installing contractor's obligation, as with any fire sprinkler system field inspection, to comply with National Fire Protection Association (NFPA) 13 requirements for the installation of spare fire sprinklers. Since the Victaulic FL-SC/VS2 flexible fire sprinkler is a “fire sprinkler”, at least one spare Victaulic FL-SC/VS2 flexible fire sprinkler must be included with the fire sprinkler system spare head box and stored in an FFD approved manner, consistent with the requirements of the Fire Prevention Manual Section 405.039, Fire Sprinkler Systems Spare Head Boxes Effective Date: April 2023 Author: Justin H. Beal, Fire Prevention Engineer Current Revision Date: 04/18/2023 Section 405.040A Next Revision (1) Date: 04/18/2026 Page 4 of 4 Additionally, where Victaulic FL-SC/VS2 flexible fire sprinklers are installed in an existing fire sprinkler system, a Victaulic FL-SC/VS2 flexible fire sprinkler is to be installed in the spare fire sprinkler head box, and the required fire sprinkler list posted within the box shall be updated to include the Victaulic FL-SC/VS2 flexible fire sprinkler. DEFINITIONS This section intentionally left blank. CROSS-REFERENCES California Fire Code (CFC), Current edition Fire Prevention Manual Section 405.039, Fire Sprinkler Systems Spare Head Boxes National Fire Protection Association (NFPA) - 13D, Standard for the Installation of Sprinkler Systems in One- and Two- Family Dwellings (current edition with California amendments)