HomeMy WebLinkAbout405.040 - Flexible Sprinkler Hoses and FittingsEffective Date: July 2021 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 7/22/2025 Section 405.040 Next Revision (1) Date: 7/22/2028 Page 1 of 2 Fresno City Fire Department 400 Prevention Manual SECTION 405.040 FLEXIBLE SPRINKLER HOSES AND FITTINGS PURPOSE The purpose of this policy is to clarify the Fresno Fire Department’s (FFD or Department) requirements regarding the design, use and installation of flexible sprinkler hoses and fittings for all automatic fire sprinkler systems. APPLICATION This policy applies to all automatic fire sprinkler system installations, within the City of Fresno (COF) and contract service areas. These requirements apply to both required and voluntarily installed automatic fire sprinkler systems. OPERATIONAL POLICY Based upon the need for uniformity in application across the Department’s diverse service delivery area, the Department has determined that when permit applicants intend to design, use, and install flexible sprinkler hoses and fittings in automatic fire sprinkler systems, they shall, at a minimum, follow the requirements noted below: 1. Prior to the installation of any flexible sprinkler hoses and fittings, in any automatic fire sprinkler system, a permit for their installation must be obtained from FFD. 2. Permit applicants are prohibited from using the “Under 20 head TI” permit process for the installation of any flexible sprinkler hoses and fittings. Each proposed installation using flexible hoses and fittings must be accompanied by plans and hydraulic calculations in accordance with the CFC and National Fire Protection Association (NFPA) 13, Standard for the Installation of Sprinkler Systems, prior to commencing work. 3. When permit applicants submit construction documents to FFD for the installation of flexible sprinkler hoses and fittings, the following items must be noted on the construction documents: I. The flexible hose make. II. The flexible hose model number. Effective Date: July 2021 Justin H. Beal, Fire Prevention Engineer Current Revision Date: 7/22/2025 Section 405.040 Next Revision (1) Date: 7/22/2028 Page 2 of 2 III. The flexible hose length. IV. The flexible hose outlet style. V. The maximum number of bends permitted for the specified flexible hose in the application and the bend radius. VI. The flexible hose installation method that will be used for the attachment to the ceiling, including the bracket assembly. As noted in NFPA 13, the construction documents must include a submittal book which has all applicable manufacturer’s installation sheets, including the listing of the materials and the installation instructions. OPERATIONAL GUIDELINE This section intentionally left blank. PROCESS This section intentionally left blank. INFORMATION As noted in the California Fire Code (CFC) the Department is permitted to specify requirements for the design, use and installation of flexible sprinkler hoses and fittings for all automatic fire sprinkler systems. DEFINITIONS This section intentionally left blank. CROSS-REFERENCES California Fire Code, Currently adopted edition. NFPA 13, Standard for the Installation of Sprinkler Systems, Currently adopted edition.